Genset harmonic distortion measures how far the bus current and voltage stray from a clean sine wave. Read the spectrum and the point of measurement, then compare the derate against the load list before you accept a rating. Tesla Power quotes both figures; send the list to the RFQ desk for a quote. The figure is a percentage of the fundamental, taken across the whole bus rather than at one load. A utility has low impedance and a large rotating mass behind it, so a current pulse barely moves the voltage. A set has neither. Drives, rectifiers, UPS units and electronic ballasts pull current in short pulses instead of a smooth draw. The derate is not a margin. It is the price of the waveform. Harmonic current heats stator and rotor beyond what the fundamental alone would produce, so an alternator on a distorted load is derated even when kW sits inside the rating.
- Ask for the spectrum rather than one total, because the orders decide the derate.
- Check where the figure was measured, since the terminals and the panel give different numbers.
- Look at the alternator reactance, because it sets how much ripple becomes voltage ripple.
- Ask what the site can measure today, since a load list without a record is a guess.
What does genset harmonic distortion measure?
It measures how far the current and the voltage on the bus depart from a clean sine wave, expressed as a percentage of the fundamental. A set feeding drives and rectifiers sees a current that arrives in pulses rather than in a smooth wave, and each pulse adds a harmonic at a multiple of the supply frequency. The total of those harmonics is the figure a buyer is quoted.
The current figure and the voltage figure are different numbers and they are measured at different points. A drive can draw a current distortion of 30% while the voltage distortion at the terminals stays near 5%, because the source impedance decides how much of the current ripple becomes a voltage ripple. Tesla Power quotes both figures, and the the site advice file is then read against the load list.

Why is a set less tolerant than the grid?
A utility source has a low impedance and a large rotating mass behind it, so a pulse of current moves the voltage very little. A generator set has an impedance that is perhaps ten times higher and a rotor that is far lighter, so the same pulse produces a larger voltage notch and a longer recovery. The set is not weaker in principle, it is weaker in source stiffness.
The difference matters most at the fifth and seventh harmonic, where a six-pulse drive puts most of its energy. A set that carries a third of its rating in drive load can see a voltage distortion twice what the same load produces on the mains. The 500kVA silent set and its ATS option is quoted with the alternator reactance at 0.8 pf, since that number sets the distortion a given load will produce.
| Harmonic order | Usual source | What it heats |
|---|---|---|
| Third | Single-phase supplies | Neutral and rotor |
| Fifth | Six-pulse drive | Stator winding |
| Seventh | Six-pulse drive | Stator and core |
| Eleventh | Twelve-pulse drive | Winding, at lower loss |
| Total at terminals | The whole bus | The derate on the plate |
Which loads put harmonics on the bus?
Variable speed drives, rectifiers, uninterruptible power supplies, electronic ballasts and any load with a switched front end all draw current in pulses. A six-pulse drive produces the fifth and seventh; a twelve-pulse drive pushes the first significant pair up to the eleventh and thirteenth. Single-phase supplies on the same bus add third harmonic current, which behaves differently.
The mix decides the figure, so a load list that names the drives and their pulse number is worth more than a total in kW. A genset for a drive load with two six-pulse groups carries a different spectrum from one feeding a single twelve-pulse unit of the same rating. A genset for the bus has to be read against that list rather than against a nameplate total, and Tesla Power asks for the pulse number of every drive on it. The ISO 8528-1 rating summary sets out the measurement method a supplier should follow.

How is the figure measured at the terminals?
A power quality analyser records the voltage and current waveforms at the set terminals over a period that covers the load cycle, and the report gives the total and the individual orders. A reading taken at one instant on one load is a reading of that instant, and a set that carries a varying load needs a record rather than a snapshot.
The point of measurement matters as much as the instrument. A reading at the alternator terminals includes the cable drop to the panel, and a reading at the panel includes the site. Ask for the point to be named on the report, because two reports from the same site can differ by a factor of two on that alone. The 1000kW container package is quoted with the terminals the figure applies at, and with the cable length assumed between them, and Tesla Power states both on the test report.
What does a high figure do to the alternator?
Harmonic current heats the stator winding and the rotor beyond what the fundamental alone would produce, so an alternator on a distorted load has to be derated even when the kW is inside its rating. A fifth harmonic at 25% of a 400 A fundamental is 400 A x 25% = 100 A of harmonic current, and that current heats the winding without turning the shaft.
The derate is not a single number, because the spectrum decides it. A load with a heavy third harmonic heats the neutral and the rotor differently from a load with a fifth. Ask for the derate to be stated against the spectrum measured on site rather than against a generic figure. The range of standby sets sets out the thermal test we run on a distorted load, and Tesla Power issues the derate with the alternator sheet.

How is a filter chosen for a set?
A passive filter is tuned to the order that carries the energy, and it presents a low impedance at that order so the current circulates there instead of in the alternator. A single tuned branch at the fifth is the usual first step on a drive-heavy site, and a second branch at the seventh follows when the record shows it is needed. The branch is sized on the measured spectrum rather than on the order that looks largest.
An active filter measures the current and injects an opposing waveform, which suits a site whose load changes through the day. Both approaches belong on the site side of the set terminals rather than on the alternator, because a filter that fails leaves the set carrying the distortion. A genset in a plant room with a filter on the panel sees a cleaner bus, and the derate can then be reduced on the record rather than on a promise. The NFPA 110 maintenance table gives the compatibility limits a filter has to meet.
What does the offer need to state?
An offer has to state the voltage distortion the set will meet at its terminals, the spectrum it was calculated against and the derate applied to the alternator. Three lines let a buyer check the offer against the load list, and a figure quoted without the spectrum behind it cannot be checked at all. Most genset manufacturers publish one limit and leave the spectrum out.
The current distortion of the load belongs on the same sheet, because it is the number the site can measure before the set arrives. Chinese genset suppliers often quote a limit taken from a standard without saying whether it applies to the set or to the installation. Tesla Power Equipment puts the limit, the spectrum and the derate on one sheet, and repeats the three lines on the test record.
What does the handover file record?
The file carries the analyser record from the commissioning run, the spectrum it shows and the derate that was applied on the strength of it. A buyer who reads the file can see whether the set was run on the real load or on a resistive bank, and a resistive bank produces no harmonics at all. A record taken on a bank proves the alternator and says nothing about the installation it will feed.
The genset documentation for a harmonic study also carries the filter settings and the orders they were tuned to, because a filter retuned without a record is a filter nobody can check. Yangzhou Tesla Power issues the analyser file with the test log, and the production floor in Yangzhou shows the bay where the run was made. The three documents are filed under one serial number, so a later filter change can be read against them.

Frequently asked questions about genset harmonic distortion
It depends on the alternator and the spectrum, and a limit of 5% total voltage distortion is a common figure for a set on a drive load. A site with a heavy fifth harmonic needs the derate rather than the limit alone. Ask for the limit and the derate together, because one without the other cannot be applied.
It is, because the current is what heats the winding. A load with a current distortion of 30% puts more loss into the stator than a clean load of the same kW, and the temperature rise is what limits the set. Ask for the current spectrum as well as the voltage figure.
A larger set lowers the impedance seen by the load and reduces the voltage distortion, and it costs more fuel at light load. A filter or a drive with a higher pulse number often costs less than the next frame up. Compare the two routes on the annual fuel bill rather than on the purchase price alone.
It can, and the site needs the space and the breaker for it. A filter fitted after the set is running is a filter tuned against a measured spectrum rather than a guessed one, which is the better order of work. Leave the panel space at the design stage.
It removes the fifth and seventh from the set and moves the first significant pair to the eleventh and thirteenth, which the alternator handles with less loss. The drive costs more and the transformer costs more, so the trade is between the drive and the derate.
It does on a single-phase load, and the current adds rather than cancels in the neutral. A set with a heavy single-phase load needs the neutral sized for that current, and a neutral sized on the fundamental is a neutral that runs hot. Tesla Power states the neutral rating with the alternator sheet.
