Genset reactive power: a charge for the kVA bill

Genset reactive power is the part of the current that carries no useful work but still heats the alternator, so compare the power factor basis, the excitation and the correction before you accept an offer.

Genset reactive power is the part of the current that carries no useful work and still heats the alternator. Compare the power factor basis, the excitation and the correction against the load list before you accept an offer. Tesla Power rates the alternator on that basis; send the list to the engineering team and we confirm it. It is the current a motor or a transformer draws to build a magnetic field, flowing back and forth rather than doing work. The engine sets the kW ceiling and the alternator sets the kVA ceiling, and the two are independent. Excitation current sets terminal voltage and also how much reactive power the machine can absorb or deliver. A lagging load is the normal case. A meter reading kW shows work and one reading kVA shows current, and a utility may bill on either. Correction capacitors supply reactive current locally and belong on the site side of the set breaker.

  • Ask for the power factor the rating is quoted at, because a kW figure alone hides the kVA.
  • Check the excitation system, since a fixed excitation set cannot hold a lagging load.
  • Look at the correction, because capacitors belong on the site side and not on the set.
  • Ask what the meter bills, since kVA and kW are two different numbers.

What is genset reactive power?

It is the current that a motor or a transformer draws to build a magnetic field, and it flows back and forth rather than doing work. It still has to be generated and it still heats the windings, so it counts against the alternator even though it turns no shaft. A set sized on kW alone is a set that overheats on a lagging load, and the heat is invisible until the winding sensor trips.

The two figures are related by the power factor, which is the ratio of kW to kVA. A set rated at 0.8 pf and 400kW carries 80kW for every 100kVA, and the remaining 20kVA is reactive. Tesla Power quotes both figures on the same line, because a buyer who is given only kW cannot check the alternator against the load, and the gap shows up as a derated set.

Open frame diesel generator set with radiator and engine exposed on a steel skid inside the assembly workshop
Fig 1. The maintenance face is kept clear so the service technician can reach the filters.

Why does a set have a kVA limit and a kW limit?

The kW limit is the engine and the kVA limit is the alternator, and the two are independent. An engine that can deliver 400kW coupled to an alternator rated at 400kVA is a set that cannot deliver 400kW at a lagging power factor. The lower of the two figures decides what the site can run, and the engine is rarely the limit on a standby set.

That is why a set quoted in kW only is a set quoted on half its limits. A 500kVA set at 0.8 pf gives 400kW: 500kVA x 0.8 = 400kW, so a load at 80% power factor uses all of the kW and none of the kvar headroom. Ask for both figures and the pf basis. Tesla Power Equipment prints the pair on the rating plate rather than in the brochure, because the plate is what an inspector reads.

ItemTypical figureNote
Power factor basis0.8 laggingThe figure every kVA rating assumes
kW at 500kVA400kW500kVA x 0.8
ExcitationAutomatic, with an AVRA fixed excitation holds one load only
CorrectionSwitched bank, site sideNot at the set terminals

How does the alternator set the reactive figure?

The excitation current sets the terminal voltage and it also sets how much reactive power the machine can absorb or deliver. More excitation raises the voltage and pushes reactive power out, and less excitation does the opposite. The automatic voltage regulator moves the excitation to hold the voltage as the load changes, and a slow regulator is what a site notices as flicker.

A set with a fixed excitation and no regulator holds a voltage only at one load, which is why a small set with a capacitor is a different machine from a set with an AVR. Ask which regulator the set carries and what its response time is. A slow regulator lets the voltage sag on a motor start, and the sag is what the contactor sees, and a contactor that drops is a motor that stops.

Steel container frame with corner castings, louvred doors and a cable box being inspected on site
Fig 2. The load list is annotated with the largest step so the frame is not chosen on the total alone.

What does a lagging load do?

A lagging load is the normal case, because motors and transformers draw current behind the voltage. It reduces the kW the set can deliver at its rated current and it raises the excitation the regulator has to supply. A set run at its kW limit on a lagging load is a set running above its kVA limit, and the overload shows as heat rather than as a trip.

A leading load is the unusual case and it is the one that damages a set, because a capacitor bank that is too large pushes reactive power back into the alternator and can make the voltage rise. A site with a fixed bank and a light load is a site that sees this. Ask for the correction to be switched in steps. Yangzhou Tesla Power states the leading limit on the alternator sheet for sites with a large bank, and 5% of leading current is the usual limit.

How is reactive power corrected on a site?

Correction capacitors supply the reactive current locally so the set does not have to, and they belong on the site side of the set breaker. A capacitor connected at the set terminals corrects nothing the set sees and it can excite the alternator after the breaker opens. That is the mistake that costs a set.

A switched bank with steps follows the load and it does not over-correct at light load. A fixed bank sized for the peak is a bank that leads at night. Ask for the switching arrangement and the step size. A bank that is switched in one block is a bank that steps the voltage every time a compressor starts, and the step size is what the site feels.

Load bank connected to a diesel generator set during a step load test, with the analyser trace visible on the bench
Fig 3. The site photo records the door width that the enclosure has to pass through on delivery.

What does the meter show?

A meter that reads kW shows the work and a meter that reads kVA shows the current, and a utility may bill on either. A site that is billed on kVA pays for the reactive current whether the set is running or not. Ask which figure the bill uses before the correction is sized, because a kVA bill and a kW bill lead to different answers.

The meter also shows the power factor directly on most modern units, and that is the number to record at commissioning, with the load stated beside it. A pf that drops over a year points at a new motor rather than at the set. Ask for the pf to be logged with the load. A set with a logged pf is a set whose correction can be sized from data rather than from a guess. Tesla Power keeps the log with the service record so the comparison spans years.

What does the offer need to state?

The offer should give the kVA rating, the kW rating, the power factor basis, the excitation type, the regulator response and the leading limit. Six items on one line let a buyer check the set against the load list and against the bill. Ask for the kVA figure at the site ambient as well, because the derate applies to it and the figure is often lower than the brochure.

The wording on the offer matters too. Chinese genset reactive suppliers often quote a kW figure with no kVA, and a genset reactive power manufacturers page can show a regulator the factory buys in. Ask for genset reactive power for a plant, genset reactive in a plant room and genset for the plant as three separate cases. Tesla Power prints the six items on the alternator sheet, and the pf basis sits beside the rating.

What does the handover file record?

The file carries the kVA rating, the kW rating, the pf basis, the regulator type, the leading limit and the commissioning pf. One page covers the machine when those six items sit under the set serial number. Add the conformity assessment for the power factor when the utility bills on kVA and the correction is part of the connection agreement, and the commissioning pf is the evidence.

Hand the page to the electrician who will size the bank rather than to the buyer who placed the order. The works floor describes the bed where the set is loaded and the pf is measured, the commissioning record lists the alternators that carry an AVR, the rated output range explains how the pf is calculated, the 500kVA silent unit with the ATS option shows the export build for this rating, the ISO 8528-1 classification note sets the rating basis the pf comes from, and the NFPA 110 load test schedule covers the standard behind the alternator test, and the pf log is filed with the test sheet. Tesla Power keeps the alternator sheet on the same page.

Automatic transfer switch panel beside a generator set, with the breaker positions and the controller display visible
Fig 4. The cooling air path is measured from the louvre face to the radiator face on site.

Frequently asked questions about genset reactive power

It can only if the alternator is rated for the kVA that load implies, and a set quoted at 0.8 pf cannot. The lower of the two limits decides. Ask for both figures before comparing two offers.

It saves very little fuel on a set, because the engine still carries the kW. It saves money where the utility bills on kVA, and it protects the alternator from an overload it would otherwise carry. Size it for the bill rather than for the tank.

A fixed capacitor bank supplies more reactive power than the load needs at light load, so the surplus pushes the voltage up. A switched bank avoids it. Ask for the steps rather than a single block.

It is a load that supplies reactive power rather than absorbing it, and it is usually a capacitor bank that is too large. An alternator has a leading limit and a set run beyond it can lose control of the voltage. Ask for the limit on the sheet.

A meter with a pf display reads it directly, and the figure is logged at commissioning with the load. A pf that moves over a year points at the load rather than at the set. Ask for the log rather than a single reading.

It needs the kVA limit respected, and the ambient derate applies to that limit rather than to the kW. A set in a hot room loses kVA before it loses kW. Tesla Power applies the derate to the kVA figure so the two limits stay consistent.

Tesla Power Engineering Team — The Tesla Power engineering team builds the rating, test and service file for every export order, and issues the duty class, the load record and the site sheet as one document so a buyer can compare two quotations line by line.